PROMAG50Electromagnetic flow meter quick setting operation
Key Definition:
1,""key: menu up, data value;
2,"-"key: menu down, data impairment;
3,"E"key: enter lower level menu, confirm operation and save data;
4,"/-"key: Return to the last menu.(refers""Keyand"-"keys pressed simultaneously)
basic operation steps:
1,open the cover,"E"the key to enter the setting menu;
2,""key twice outnow"GROUP SELECT""E"key in, outnow"SETUP COMMISSION"
QUICKSETUP NO
3,""Key,"-"Keyand"E"key bit-by-bit inputcode"0050", finally."E"the key to confirm.
4,makeused""Keyand"-"key,"E"key to enterParameter Item,Use""Keyand"-"key to set parameters, after setting"E"the key to confirm. (Refer to the specific menuon the instructionsQuick Settings Menu)
5,parameters"/-"key and protecthold3seconds to return the measurement status.
Quick Setup Menu Description:
1,After the instrument is powered on and stabilized, open the cover"E"key to enter the menu group, displayindication"GROUP SELECT"
MEASURINGVALUES
2,""key appears twice"GROUP SELECT""E"key in, outnow"SETUP COMMISSION"
QUICK SETUP NO
3,""Key,"-"Keyand"E"key bit-by-bit inputcode"0050", finally."E"the key to confirm.
4,re-outnow"SETUP COMMISSION",""key change"SETUP COMMISSION",Ekey is correct
NO
recognition.
5, obviousShown"LANGVAGE"select the language as English,"E"key to confirm, if you need to select other languages firstused""Keyand"-"
NO
key selection,againused"E"the key to confirm.
6,showShown"PRE-SETTING","E"key OK. Keep it now set.
"ACT-SETTJMG"
7,showShown"NIT VOLME FLOW", availableused"/-"Keyand"E"key to change the volume flow unit, and finallyused"E"
"M3/h"
the key to confirm.
8,showShown"MEASURING MODE"the way to select the current output, you canused""key selection
"STANDARD"
"STANDARD"Standard"SYMMETRY"symmetrical type, usually selectedselection"STANDARD"standard type,"E"the key to confirm.
9,showShown"SEECT OVTPUT"select signal output as current output as current output, orused""key selection
CURRENT OUTPUT
FREQ/PULSEfrequency pulse output, after selectionused"E"the key to confirm.
10,is obviousShown"ASSIGN CURRENT"indicates that the current output is volume flow,"E"confirmation.
VOLUMEFLOU
11,is obviousShown"CORRENT SPAN"is the current output4-20mAbandHARTagreement,"E"the key to confirm.
4-20mA HRAT
12, obviousShown"VALVE 20mA"used"/-"Keyand"E"key outputs the volume flow value at full range, and the flow unit must be
XXXXX X/X
must be consistent with the display unit, and then"E"the key to confirm.
13,is obviousShown"TIME ENSTANT"time constant is usually set5seconds,used""key setting5seconds,used"E"key to confirm;
1.00S
can also be changed to other values according to the actual situation.
14,is obviousShown"FAILSAFE MODE"is the current output when the alarm, optionalselection"MIN CURRENT"Alarm current lower limit;"MAX CURRENT"alarm current upper limit (can be set according to actual needs);"HOLD"hold the previous measured value of the alarmor"ACTURAL"According to the actual measured value output, it is recommended to selectselection"MIN CORRENT"or"MAX CORRENT",used"E"the key to confirm.
15,is obviousShown"SETUP""SETUP COMMISSIONG","E"key to exit.
COMPCETE NO
16,at the same time,""Keyand"-"key and protecthold3seconds to return to the measurement state.
17,is obviousShown"OPEARATION MODE"Select Output Mode"FREQUENCY"frequencyor"PULSE"pulse, can be set as needed.
18,is obviousShown"ASSIGN FREQUENCY", which represents the frequency output as volume flow,"E"the key to confirm.
VOLUME FLOW
19,is obviousShown"END VALE FREQ"select the full-scale output rate, which cannot be exceeded.over1000Hz,used"E"the key to confirm.
20,is obviousShown"VALUE Fmax"enter the full-scale volume flow value,"E"the key to confirm.
XXXXXX
21,is obviousShown"OVTPUT SIGQNAL"select frequency signal is a passive positive pulse.
PASSLUE-OPSITIVE
can also choose passive negative pulsepunch"PASSIVE-NEGATIVE"."E"the key to confirm.
22,is obviousShown"TIME CONSTANT"The usual time constant is setfixed5seconds,used""key confirmation, can also be based onprocess requirements.
23,is obviousShown"FAILSAFE MODE"is no frequency signal output when the alarm,"E"the key to confirm.
FALLBACK VALUE
24,is obviousShown"ASSIGN PULSE"indicates that the pulse output is volume flow,"E"the key to confirm.
VOLUMEFLOW
25,is obviousShown"PULSE VALVE"InputPulse equivalent, note that the unit is consistent with the cumulative unit,"E"the key to confirm.
XXXXX
26,is obviousShown"PULSE UIDTH"is the pulse width, according to the factory setting10.00s,"E"the key to confirm.
10:00
27,is obviousShown"MAX POLSE FREQ"is the maximum output pulse frequency, which can be adjusted as required, but shall not exceedover1250Hz.
28,is obviousShown"OVT PUT""SIGNAL"The output is passive positive pulse, or optionalselectionPASSIVE-NEGATIVENone
PASSIVE-POSITIVE
source negative pulse, usually selected as passive positive pulse,"E"the key to confirm.
29,is obviousShown"FAILSAFE MODE"that is, when the alarm pulse output according to the factory settings,"E"the key to confirm.
FAUBACK VALUE(Pulse output is zero in case of alarm)